The control room of a CHP (Combined Heat and Power) installation houses various electrical components, including the control panel and main power distribution panel. These panels generate heat during operation. To prevent the room temperature from rising too high, effective heat removal is required.
For this project, Ventinet supplied an EC fan to remove heat from the control room. The fan is installed high in the wall of the outdoor enclosure and controlled by a thermostat. This ensures that ventilation is adjusted to the temperature inside the room.
Heat removal from the control room
A CHP installation generates electricity and heat simultaneously, for example by means of a gas-powered generator. The heat produced can then be recovered and used for other purposes. In this project, the installation is housed in an outdoor enclosure. The control room is separated from the gas generator set by an internal partition wall. During operation, the generator set produces a considerable amount of noise.
The outer walls of the enclosure are also designed to provide sound insulation. They consist of two steel panels with 100 mm of insulation material in between.
The control panel and main power distribution panel are located in the control room. Both panels generate radiant heat. To remove this heat, the EC fan is installed high in the wall. This position allows the fan to extract warm air from the upper part of the room.
Air supply and extraction for cross-flow ventilation
Effective heat removal depends not only on the position of the fan but also on the supply of fresh outdoor air. For this application, the air supply and extraction points have deliberately been positioned on opposite sides of the control room.
The airflow is arranged as follows:
- Air extraction: The EC fan is installed high in the wall. An external weather louvre is fitted on the outside of the enclosure to prevent direct rain ingress.
- Air supply: A second weather louvre is installed low down in the access door on the opposite side of the room. Fresh outdoor air enters the control room through this louvre.
By introducing fresh air at a low level on one side and extracting warm air at a high level on the opposite side, a cross-flow ventilation pattern is created. This allows fresh outdoor air to move through the control room while the warm air is extracted.
EC fan with thermostatic control
The fan does not need to run continuously at full speed in this application. A thermostatic control system was therefore selected. Depending on the temperature in the control room, the fan switches on automatically and its speed is continuously adjusted. If the temperature rises only slightly, the fan runs at a lower speed. When more heat needs to be removed, the fan speed increases accordingly.
EC technology makes this stepless speed control possible. This allows the airflow to be adjusted to the actual heat load in the room. Interested in the possibilities? Explore our range of EC fans.
Selecting the right fan for heat removal
When selecting a fan, we look beyond the required airflow capacity alone. Factors such as the available installation space, the position of the air supply and extraction points, and the required control method also play an important role.
For this project, we selected the VN-Wall EC-C, an axial wall fan with an EC motor. The fan is mounted directly into the wall of the outdoor enclosure and extracts warm air from the control room.
Effective heat removal in a CHP control room depends on more than just the fan capacity. The positioning of the fan, the supply of fresh outdoor air and the control method all contribute to the airflow and temperature management within the room. By considering these factors together, a suitable ventilation solution can be selected for the specific installation.
At Ventinet, we combine technical product knowledge with practical application advice. This allows us to recommend suitable fans and configurations for a wide range of applications, including heat removal from technical rooms and control rooms.
Looking for a fan to remove heat from an industrial environment? Get in touch with our team to discuss your application.